Cable Selection For Borehole Motors

Here’s a practical, engineering-grade cable selection chart to help you choose 4-core submersible cable for borehole pump installs. It shows the maximum recommended cable length (meters) for common copper cable sizes to keep voltage drop ≤ 5% at 50 Hz. Use the single-phase (230 V) table for 0.37–2.2 kW and the three-phase (400 V) table for 0.37–45 kW.

Assumptions (conservative & field-ready)

  • Copper cable; resistance adjusted for operating temperature.
  • Typical running load:
    • 1-Ph motors: PF≈0.90, η≈0.75
    • 3-Ph motors: PF≈0.85, η≈0.90
  • Voltage drop target: ≤5% of supply (SANS-aligned rule of thumb).
  • “4-core” usage:
    • 1-Ph: you’ll typically use 3 conductors (L, N, E) and keep one spare/aux.
    • 3-Ph: use 3 phase cores + earth.
  • If your actual motor nameplate current is higher, or your start/run gear adds extra loss, choose the next cable size up.

Single-phase 230 V (50 Hz), 0.37 kW → 2.2 kW

Cells = Max cable length (m) for ≤5% drop.

kWNominal A1.5 mm²2.5 mm²4 mm²6 mm²10 mm²16 mm²25 mm²35 mm²50 mm²
0.372.417429146669911661865291540815831
0.553.51171963144717861258196227473925
0.754.886144230345575919143320072866
1.107.05910016024040064099713961995
1.509.7437211617429046472310121446
2.2014.2294978117196313490686980

Tip: Many 1-Ph submersible installs in the 1.1–1.5 kW range at 60–100 m do well with 6 mm²; at >100 m, step to 10 mm².


Three-phase 400 V (50 Hz), 0.37 kW → 45 kW cable selection

Cells = Max cable length (m) for ≤5% drop.

kWNominal A1.5 mm²2.5 mm²4 mm²6 mm²10 mm²16 mm²25 mm²35 mm²50 mm²
0.371.4591986157723663944631098601380519721
0.552.139465710511577262842056570920013150
0.752.8295492787118019703150492769119880
1.104.120133553680413402140335047006723
1.505.515025040060010001600250035005000
2.208.01031722754126871100172024103440
3.0010.876127203304506810127517902550
4.0014.3589915823739563299614001990
5.5019.6427111417128545671810001425
7.5026.73152831242073315217311039
11.038.921335481134215338474672
15.053.01525406099159251352499
18.565.41220324879128201282399
22.077.71017274167108170239339
30.0106.071220304775118166235
37.0130.66101624386195134190
45.084.9*916263965105164230328

*For 45 kW the nominal current shown is for η≈90%, PF≈0.85 at 400 V; your nameplate may vary by manufacturer.


How to use this cable selection chart (quick method)

  1. Find motor kW and check the Nominal A is close to your nameplate (if it’s higher, upsize cable).
  2. Pick your planned cable length (depth + horizontal run + panel distance).
  3. Choose the smallest mm² that gives a max length ≥ your run.
  4. If starting is “hard” (weak supply, DOL on long runs, high static head), go one size larger.

Practical notes for boreholes cable selection

  • Cable type: Use submersible pump cable 600/1000 V (flat or round), UV-resistant for the rising main and above-ground section.
  • Splices & joints: Every joint adds resistance — if you have multiple splices, treat your run as longer or upsize.
  • Earth continuity: Always run a dedicated earth core to the motor frame/ground lug.
  • Protection: Size breakers/overloads to motor FLA (per nameplate) and cable’s current-carrying capacity (installation method).
  • Standards: South Africa’s SANS 10142-1 generally targets ≤5% voltage drop on final circuits; many pump OEMs prefer even tighter for reliable starting.
Shopping Cart
Scroll to Top